The Petroleum Act, 1886, 12 of 1886, (Rep., Act 8 of 1899)

Section 2. Preparing the test-lamp

Repealed or not in force · As amended up to 2026-08

2. Preparing the test-lamp.—The test-lamp is fitted with a piece of cylindrical wick of such thickness that it fills the wick-holder, but may readily be moved to and fro for the purpose of adjusting the size of the flame. In the body of the lamp, upon the wick, which is coiled within it, is placed a small tuft of cotton wool, moistened with petroleum, any oil not absorbed by the wool being removed. When the lamp has been lighted, the wick is adjusted by means of a pair of forceps until the flame is of the size of the bead fixed on the cover of the oil-cup; should a particular test occupy so long a time that the flame begins to get smaller, through the supply of oil in the lamp becoming exhausted, three or four drops of petroleum are allowed to fall upon the tuft of wool in the lamp from the dropping bottle or pipette provided for that purpose. This can be safely done without interrupting the test. 2. Preparing the sample for testing.—About ten fluid ounces of the oil, sufficient for three tests, are transferred from the bottle into which the sample has been drawn to a pint flask or bottle, which is to be immersed in water artificially cooled until a thermometer, introduced into the oil, indicates a temperature not exceeding 50° Fahrenheit. III.—Directions for preparing and using the Test-apparatus.